器件名称:
600E-3CL-5.5
功能描述:
E Rated Medium Voltage Fuses
文件大小:
384.36KB 共5页
简 介:
E Rated Medium Voltage Fuses Current Limiting “E” Rated fuses have time current characteristics designed to provide current limiting protection for power transformers, potential transformers, power centers, feeder centers, and unit sub stations. When properly applied, they can protect against high and low value fault currents. NEMA Standards for “E” rated medium voltage fuses require that fuses rated 100E or less open within 300 seconds (5 minutes) when subjected to an RMS value of 200-240% of the fuse’s continuous current rating; and fuses with an “E” rating larger than 100E must open within 600 seconds (10 minutes) when subjected to an rms current of 220-240% of the fuse’s continuous current rating. These values establish one point on the time-current curve. Application Note: Since these fuses are used for the protection of general purpose circuits which may contain transformers, motors, and other equipment producing inrush and/or overload currents, fuses should generally be rated at 140% of the normal full load current, and circuits should be analyzed to ensure that system load currents will not exceed the current rating of the fuse. CHARACTERISTICS Voltage Rating: 2,400 volts – 38,000 volts Current Range: 10E – 600E OPTIONS I I Hermetically Sealed for use in hazardous locations (add “S” suffix to part number) Clip-lock (CL) and bolt-in styles available. 3"DIA 6.38" 9.75" Dim.A (Clip Center) Dim.B FIGURE 14 FIGURE 15 FIGURE 16 E RATED Catalog Number 10E-1C-2.7……